FT-PD
Fire rated steel doors and partitions
Cold-rolled steel framing for building entrances, lift lobbies, server rooms and corridors — the places a compartment boundary has to hold and people still have to get through.
E120EI30EW120
120min
Integrity
120min
Radiation
Steel systems made by Firetec. The frame is specified together with the glass it holds, rather than assembled from whatever is available.
Introduction
A fire rated door has one job: it holds a compartment boundary. It stops fire and smoke crossing from the room that is burning into the route people are leaving by, for as long as the fire strategy needs. Everything else — the ironmongery, the vision panel, the finish — is in service of that.
The FT-PD range is built on cold-rolled galvanised steel profiles rather than a proprietary composite, so a fabricator can cut, weld and glaze it with the equipment already in the shop, and a specifier can read the section. A door frame and a full-height partition head are the same family with a different depth, and it is the same steel system as the FT-CW curtain wall — so a project can carry one system from the facade to the core wall to the lift lobby.
NABL accredited laboratory, covered by ILAC
Tested in a furnace at a NABL accredited laboratory, to IS standards. The range holds a two-hour fire rating — 120 minutes of integrity and 120 minutes of radiation control — and is classified E120 / EI30 / EW120.


Twelve profiles
What the system is made of
Firetec’s twelve door and partition profile sections, numbered as the drawing has them.
After the test
What a fire test looks like
Photography from the fire test.

Specification
What the reports record
Every row names its source. Where the reports, the catalogue and the previous website disagree, this table prints every candidate value and flags the row rather than picking one.
| Classification | E120orEI30orEW120 | NABL accredited laboratory |
|---|---|---|
| Integrity achieved | 120 min | NABL accredited laboratory |
| Radiation achieved | 120 min | NABL accredited laboratory |
| Test standard | IS 16945:2018 | NABL accredited laboratory |
| Material | Cold-rolled galvanised steel | Firetec |
| Profile face width | 45–60 mm | Firetec |
| Profile depth | 50–110 mm | Firetec |
| Finish | Factory-applied paint, powder coat, or a stainless finish | Firetec |
| Profile sections | Twelve numbered profile sections | Firetec |
| Typologies | Nine configurations | Firetec |
E · EI · EW
Integrity, insulation and radiation are three different things
They are measured in the same test and they fail at different times. Most fire rated glazing material in this market treats them as one number with a bigger version, and reading a specification that way is how a building ends up with the wrong product in it.
Which is why this range is classified E120 / EI30 / EW120. It holds a two-hour fire rating — 120 minutes of integrity and 120 minutes of radiation control — tested in a furnace at a NABL accredited laboratory, to IS standards.
Nine configurations
Door typologies
Single and double leaf, with side-lites, over-panels and arched heads, in single and double action and on an offset pivot. Drawn at the 60 mm frame face on a 900 × 2100 mm leaf, in standard swing notation.
Where it goes
Sectors this system is specified into
The argument you have to make to a consultant changes with the building type. These are the three this range comes up in most often.

3
System lines, one steel system
Commercial offices
Lift lobbies, core walls and facade, specified to one steel system.

180min
FT-PD integrity, defend in place
Hospitals
Protected escape routes and daylight in corridors that cannot be closed off.

15kW/m²
The EW threshold, at one metre
Data centres
Compartmentation around white space and plant rooms, with vision panels that survive the rating.